Page 1© 2004 Lennox Industries Inc.Dallas, Texas, USALitho U.S.A.504,926M5/2004LZP-2ZONE CONTROL PANELINSTALLATION INSTRUCTIONS FOR ZONE CONTROL PANEL
TroubleshootingDETECTING HVAC SYSTEM PROBLEMSSymptom Possible SolutionPressure switch open.Consult condensing unit manual for possible cause.Compresso
Page 11No power to control panel. Green “Normal Flashing”LED should be blinking, if not apply power to 24VAC inputs of control panel. Check fuse.Singl
Page 12B220345810006259Troubleshooting (continued)CHECKING THERMOSTAT VOLTAGESDISCHARGE AIR SENSOR CHECKOUTUsing a digital voltmeter (DVM) measure the
Page 2Application• Two zones• Single-stage electric or gas furnace• Single-stage air conditioner• Multi-stage equipment can be used provided that itst
Page 3Installation (continued)FIGURE 3 – DISCHARGE AIR SENSOR LOCATION15"D/3WDFRONTIMPORTANT: The discharge air sensor is required.If a short or
Page 46. Install the thermostats. Refer to the instructionsprovided with the thermostat.Any 24-volt electronic thermostat with a “C” (24 VACcommon) te
Page 5Bypass Damper SizingWhen fewer than the maximum number of zones arecalling for heating or cooling, an excess volume of air isdelivered, and beca
Page 6Field WiringDIAGRAM 1 – FIELD WIRINGDIAGRAM 2 – DAMPER WIRING WITH SEPARATE TRANSFORMER
Page 7Pin Jumper Settings (see Figure 5)LEDsELECTRIC/GAS: If electric heat is to be used, move thejumper to the “ELECT” position. This will turn on th
Page 8A Time Delay Override (TDO) button is available on thecontrol panel to speed up the internal timer by a factorof 60 for system checkout. One sec
Page 9CONTINUOUS FAN OPERATIONA call for Fan from any zone will initiate the Gequipment output terminal. The normally open (NO)damper terminal at all